Call us at (866) 330-1709 In Stock & Shipped Fast All Brands & Products by Quote HVAC Promotions & Seasonal Specials Need Help? Contact Support

Condenser Water System Design: Piping, Pumps, and Controls

Condenser Water System Design: Piping, Pumps, and Controls

1. Introduction

Condenser water systems are integral to the efficient operation of water-cooled chiller plants, which are widely used in commercial, industrial, and institutional buildings for air conditioning and process cooling. These systems are responsible for rejecting heat absorbed by the refrigerant in the chiller's condenser to the ambient environment, typically via a cooling tower. The proper design of a condenser water system is critical for optimizing energy efficiency, ensuring reliable operation, and minimizing the overall life cycle cost of the cooling plant [1].

The system's primary function is to circulate water through the chiller's condenser, where it picks up heat from the hot refrigerant, and then transport this heated water to a cooling tower. In the cooling tower, the heat is dissipated to the atmosphere through evaporative cooling, and the cooled water is then returned to the chiller to repeat the cycle. This continuous heat rejection process is essential for maintaining the chiller's performance and preventing overheating.

Condenser water systems are employed in applications requiring significant cooling capacities, where air-cooled chillers would be less efficient or impractical due to size and noise constraints. Their importance lies in their ability to provide stable and efficient heat rejection, directly impacting the chiller's coefficient of performance (COP) and the building's overall energy consumption. A well-designed system ensures that the chiller operates at optimal condenser water temperatures, which is crucial for achieving its rated capacity and efficiency.

2. System Components

A typical condenser water system comprises several key components, each playing a vital role in the heat rejection process. Understanding the function and specifications of these components is fundamental to effective system design.

2.1 Water-Cooled Chiller

The water-cooled chiller is the heart of the cooling system, responsible for producing chilled water. It consists of an evaporator, compressor, condenser, and expansion valve. In the condenser, the hot, high-pressure refrigerant gas from the compressor transfers its heat to the circulating condenser water, causing the refrigerant to condense into a liquid. The performance of the chiller is highly dependent on the temperature of the condenser water entering it; lower entering condenser water temperatures generally lead to higher chiller efficiency.

2.2 Cooling Tower

The cooling tower is where the heat absorbed by the condenser water is rejected to the atmosphere. Cooling towers can be open-circuit (evaporative) or closed-circuit (fluid coolers). Open-circuit towers are more common due to their lower first cost and higher efficiency in many applications [2]. In an open-circuit tower, the hot condenser water is sprayed over a fill material, increasing its surface area and allowing it to come into direct contact with ambient air. A portion of the water evaporates, carrying away latent heat and cooling the remaining water. Key specifications include capacity (tons of refrigeration), flow rate (GPM), approach (difference between leaving water temperature and ambient wet-bulb temperature), and range (difference between entering and leaving water temperatures).

2.3 Condenser Water Pumps

Condenser water pumps circulate the water between the chiller's condenser and the cooling tower. These are typically centrifugal pumps, selected based on the required flow rate and total dynamic head. The flow rate is determined by the chiller's condenser water requirements, while the total dynamic head accounts for all pressure losses in the piping, valves, fittings, and equipment, as well as elevation differences [1]. Pumps can be configured in parallel for redundancy and variable flow applications. Important pump specifications include flow rate (GPM), total dynamic head (feet of water), efficiency (%), net positive suction head available (NPSHA), and motor horsepower (HP).

2.4 Piping Network

The piping network connects the chiller, pumps, and cooling tower, facilitating the flow of condenser water. Proper pipe sizing is crucial to minimize pressure drop, ensure adequate flow, and prevent excessive velocities that can lead to erosion and noise. Common pipe materials include steel (ASTM A53 Schedule 40/80), copper (ASTM B88 Type K, L, M), PVC (ASTM D2241), and polypropylene (ASTM F2389) [1]. The piping system must be designed to accommodate thermal expansion and contraction, and include provisions for drainage, air venting, and isolation.

2.5 Valves and Fittings

Various valves and fittings are used throughout the condenser water system for isolation, flow balancing, control, and maintenance. These include: * Isolation valves (e.g., butterfly, ball valves) for isolating equipment for maintenance. * Balancing valves (e.g., globe valves, circuit setters) to ensure proper flow distribution. * Check valves to prevent backflow. * Control valves (e.g., two-way, three-way) for modulating flow based on system demand. * Strainers to remove debris and protect pumps and chillers. * Expansion joints to absorb thermal movement.

Each valve and fitting contributes to the overall system pressure drop, which must be accounted for in pump sizing [1].

2.6 Water Treatment System

A water treatment system is essential for open-circuit cooling towers to prevent corrosion, scaling, biological growth (e.g., Legionella), and fouling. As water evaporates in the cooling tower, dissolved solids concentrate, increasing the risk of these issues. Typical components include chemical feed systems (for corrosion inhibitors, scale inhibitors, biocides), bleed-off (blowdown) systems to remove concentrated water, and filtration systems to remove suspended solids. Proper water treatment extends equipment life and maintains system efficiency.

3. Design Principles

Effective condenser water system design adheres to several fundamental engineering principles and criteria to achieve optimal performance and energy efficiency.

3.1 Heat Rejection Load

The primary design consideration is the heat rejection load, which is the total heat that must be removed from the chiller's condenser. This load is typically the sum of the building's cooling load (heat absorbed by the chilled water) and the heat equivalent of the chiller's compressor work. A common rule of thumb for water-cooled chillers is that the condenser heat rejection is approximately 15,000 BTU/hr per ton of refrigeration, or about 1.25 times the nominal cooling capacity of the chiller [3].

3.2 Temperature Difference (ΔT)

The temperature difference (ΔT) across the chiller's condenser and the cooling tower is a critical design parameter. For the chiller condenser, this is the difference between the leaving and entering condenser water temperatures. For the cooling tower, it's the difference between the entering hot water temperature and the leaving cold water temperature. A typical design ΔT for condenser water systems is 10°F (5.6°C), for example, 85°F (29.4°C) entering and 95°F (35°C) leaving the chiller condenser. The cooling tower is typically designed to cool water to within 7°F (3.9°C) of the ambient wet-bulb temperature (the approach) [3].

3.3 Flow Rate Calculation

The condenser water flow rate (GPM) is calculated based on the heat rejection load and the design temperature difference (ΔT) across the chiller condenser. The formula is:

Q = (Heat Rejection Load in BTU/hr) / (500 * ΔT)

Where: * Q = Condenser Water Flow Rate (GPM) * Heat Rejection Load = Total heat rejected by the chiller (BTU/hr) * 500 = A constant for water (specific heat of water * density of water * 60 minutes/hour) * ΔT = Temperature difference across the chiller condenser (°F)

For example, a 100-ton chiller (1,200,000 BTU/hr cooling capacity) with a typical condenser heat rejection of 1,500,000 BTU/hr and a 10°F ΔT would require a condenser water flow rate of:

Q = 1,500,000 BTU/hr / (500 * 10°F) = 300 GPM

3.4 Cooling Tower Sizing

Cooling towers are sized based on the heat rejection load, the design wet-bulb temperature, and the desired approach and range. A common rule of thumb is to size the cooling tower for approximately 3 GPM per ton of refrigeration, or 1.25 times the nominal chiller capacity [3]. For a 100-ton chiller, this would suggest a cooling tower capacity of 125 tons, requiring 375 GPM (125 tons * 3 GPM/ton) at a 10°F range.

4. Pipe Sizing and Hydraulics

Proper pipe sizing is paramount for efficient and reliable condenser water system operation. Undersized pipes lead to excessive pressure drop, increased pump energy consumption, and potential erosion, while oversized pipes result in higher initial costs and low fluid velocities, which can lead to sedimentation and air accumulation.

4.1 Flow Rates and Velocities

Pipe sizing is primarily based on maintaining acceptable fluid velocities and pressure drops. Recommended velocity ranges for condenser water piping are typically between 3 to 10 feet per second (fps) [4]. Higher velocities (up to 12 fps) may be acceptable for discharge piping, while lower velocities (below 3 fps) should be avoided in suction piping to prevent cavitation. The velocity can be calculated using the formula:

V = Q / (A * 0.321)

Where: * V = Velocity (fps) * Q = Flow Rate (GPM) * A = Internal Cross-sectional Area of Pipe (in²) * 0.321 = Conversion constant

4.2 Pressure Drop and Friction Loss

Pressure drop in a piping system is caused by friction between the fluid and the pipe walls, as well as by turbulence created by fittings, valves, and equipment. The total pressure drop determines the total dynamic head required from the condenser water pump. Friction loss in straight pipes can be calculated using the Darcy-Weisbach equation or empirically derived tables and charts (e.g., Hazen-Williams equation for water). The Darcy-Weisbach equation is generally more accurate and applicable to various fluids and flow regimes [1].

hf = f * (L/D) * (V^2 / 2g)

Where: * hf = Head loss due to friction (feet of fluid) * f = Darcy friction factor (dimensionless) * L = Length of pipe (feet) * D = Internal diameter of pipe (feet) * V = Fluid velocity (fps) * g = Acceleration due to gravity (32.2 ft/s²)

Friction factors (f) are determined using the Moody chart or the Colebrook equation, which account for the Reynolds number (Re) and the relative roughness of the pipe material [1].

Pressure losses through valves and fittings are typically accounted for using equivalent length methods or the 3-K method. The 3-K method provides a more accurate representation of pressure loss for various pipe sizes and flow conditions [1].

Table 1: Recommended Pipe Sizing Criteria for Condenser Water Systems

| Pipe Diameter (inches) | Flow Rate (GPM) | Velocity (fps) | Pressure Drop (ft/100 ft) | |:-----------------------|:----------------|:---------------|:--------------------------| | 2 | 30-60 | 3-6 | 2-5 | | 3 | 70-150 | 4-8 | 1.5-4 | | 4 | 150-300 | 5-9 | 1-3 | | 6 | 350-700 | 6-10 | 0.5-2 | | 8 | 700-1400 | 7-11 | 0.3-1.5 |

Note: These values are general guidelines and may vary based on specific project requirements, pipe material, and design standards.

4.3 Hydraulically Remote Run

The hydraulically remote run is the path through the piping system that presents the greatest resistance to flow, resulting in the highest pressure drop. Identifying this path is crucial for accurately calculating the total dynamic head required for the condenser water pump. This typically involves tracing the longest equivalent length of pipe, including all fittings, valves, and equipment, from the pump discharge, through the chiller and cooling tower, and back to the pump suction [1].

5. Equipment Selection

Selecting the right equipment is vital for the performance, efficiency, and longevity of the condenser water system.

5.1 Condenser Water Pumps

Pump selection involves matching the pump's performance curve to the system's required flow rate and total dynamic head. Centrifugal pumps are most commonly used. Key considerations include:

  • Flow Rate (GPM): Determined by the chiller's condenser water requirements.
  • Total Dynamic Head (TDH): Calculated from the total pressure drop in the hydraulically remote run, including static head (elevation differences) [1].
  • Net Positive Suction Head Available (NPSHA): Must be greater than the Net Positive Suction Head Required (NPSHR) by the pump to prevent cavitation. NPSHA is influenced by atmospheric pressure, static head on the suction side, and friction losses in the suction piping [1].
  • Efficiency: Select pumps with high efficiency at the design operating point to minimize energy consumption.
  • Motor Horsepower (HP): Sized to meet the brake horsepower (BHP) requirements of the pump, considering motor efficiency [1].
  • Pump Type: End-suction, in-line, or split-case pumps are common, chosen based on flow rate, head, space constraints, and maintenance considerations [1].

5.2 Chillers

While the chiller itself is not part of the condenser water system, its selection directly impacts the condenser water system design. Water-cooled chillers are selected based on cooling capacity (tons), energy efficiency (kW/ton or COP), and compatibility with the condenser water system design temperatures. The chiller manufacturer provides the required condenser water flow rate and pressure drop through the chiller condenser.

5.3 Cooling Towers

Cooling towers are selected based on:

  • Heat Rejection Capacity (Tons): Must match the chiller's heat rejection load.
  • Design Wet-Bulb Temperature: The ambient wet-bulb temperature at which the tower is designed to operate effectively.
  • Approach: The difference between the leaving cold water temperature and the design wet-bulb temperature. A smaller approach indicates a more efficient (and typically larger) tower.
  • Range: The difference between the entering hot water temperature and the leaving cold water temperature.
  • Flow Rate (GPM): The volume of condenser water circulated through the tower.
  • Fan Type and Motor: Axial or centrifugal fans, selected for efficiency and noise levels.
  • Materials of Construction: Corrosion-resistant materials are crucial due to continuous water exposure.

6. Controls and Operation

Effective controls are essential for optimizing the performance and energy efficiency of condenser water systems. The primary goal of control sequences is to maintain optimal condenser water temperatures for the chiller while minimizing pump and fan energy consumption.

6.1 Condenser Water Temperature Control

The most common control strategy involves modulating cooling tower fan speed or cycling fans to maintain a desired condenser water supply temperature to the chiller. Lowering the condenser water temperature generally improves chiller efficiency, but there is an optimal point where the energy savings from the chiller outweigh the increased fan energy. Typical setpoints for condenser water supply temperature range from 75°F to 85°F (23.9°C to 29.4°C), often reset based on ambient wet-bulb temperature or chiller load [5].

6.2 Condenser Water Pump Control

Condenser water pumps can operate at constant speed or variable speed. Variable frequency drives (VFDs) on condenser water pumps allow the flow rate to be modulated based on chiller load, significantly reducing pump energy consumption at part-load conditions. In systems with multiple chillers and pumps, sequencing controls ensure that pumps are brought online or offline as needed to match the operating chillers [1].

6.3 Chiller-Tower Optimization

Advanced control strategies integrate chiller and cooling tower operation to achieve overall plant optimization. This involves continuously adjusting condenser water temperature setpoints and cooling tower fan speeds to minimize the combined energy consumption of the chillers, condenser water pumps, and cooling tower fans. This often requires sophisticated building management systems (BMS) and predictive control algorithms [6].

7. Commissioning and Startup

Commissioning and startup are critical phases to ensure the condenser water system operates as designed and meets performance specifications. This involves a systematic process of inspection, testing, and balancing.

7.1 Pre-Startup Checks

Before startup, a series of checks must be performed:

  • System Cleanliness: Ensure the piping system is clean and free of debris. Flushing the system is often required.
  • Valve Positions: Verify all isolation valves are in the correct open or closed positions.
  • Pump Alignment and Rotation: Check pump-motor alignment and confirm correct motor rotation.
  • Electrical Connections: Verify all electrical wiring and connections to pumps, fans, and controls.
  • Water Level: Ensure cooling tower basin water levels are adequate and makeup water systems are functional.
  • Control Panel Settings: Confirm all control setpoints, sequences, and safeties are correctly configured [7].

7.2 Initial Startup Procedure

The general startup procedure involves:

  1. Fill and Vent: Slowly fill the condenser water system with treated water and thoroughly vent all air from the piping.
  2. Pump Start-up: Start condenser water pumps one at a time, checking for proper operation, flow, and pressure. Monitor for unusual noises or vibrations.
  3. Cooling Tower Fan Start-up: Start cooling tower fans and verify proper rotation and airflow.
  4. Chiller Start-up: Once condenser water flow is established and stable, start the chiller according to manufacturer guidelines. Monitor chiller operation parameters, including condenser water inlet/outlet temperatures and pressures [7].

7.3 Testing and Balancing

After initial startup, the system undergoes testing and balancing:

  • Flow Balancing: Adjust balancing valves to achieve design flow rates through each chiller and cooling tower cell.
  • Temperature Verification: Confirm that design condenser water temperatures (supply and return) are met under various load conditions.
  • Pressure Drop Measurements: Verify actual pressure drops across equipment and piping against design calculations.
  • Control Sequence Verification: Test all control sequences, interlocks, and safeties to ensure they function correctly.
  • Vibration Analysis: Perform vibration analysis on pumps and fans to detect potential issues.

8. Troubleshooting

Common issues in condenser water systems can lead to reduced efficiency, equipment damage, or system shutdown. Effective troubleshooting requires understanding symptoms and diagnostic steps.

8.1 High Condenser Water Temperature

Symptoms: Chiller tripping on high head pressure, reduced chiller capacity, high energy consumption.

Possible Causes: * Insufficient Cooling Tower Operation: Dirty fill, clogged nozzles, fan malfunction, low airflow, incorrect fan speed control. * Insufficient Water Flow: Clogged strainers, closed valves, pump malfunction, air in system, undersized pump. * Fouled Chiller Condenser: Scaling or biological growth on condenser tubes, reducing heat transfer. * High Ambient Wet-Bulb Temperature: Operating conditions exceeding design limits.

Solutions: Clean cooling tower, inspect fans, check pump operation, clean chiller condenser, verify control setpoints.

8.2 Low Condenser Water Flow

Symptoms: High chiller head pressure, pump cavitation, reduced chiller capacity.

Possible Causes: * Clogged Strainer: Debris accumulating in the condenser water strainer. * Closed or Partially Closed Valves: Isolation or balancing valves not fully open. * Pump Malfunction: Impeller damage, motor issues, incorrect rotation. * Air in System: Air pockets restricting flow, especially in suction piping. * Undersized Pump: Pump not capable of delivering design flow against system head.

Solutions: Clean strainer, check valve positions, inspect pump, vent air, re-evaluate pump sizing.

8.3 Pump Cavitation

Symptoms: Loud noise from pump (gravel-like sound), vibration, reduced pump performance, impeller erosion.

Possible Causes: * Insufficient NPSHA: Suction pressure too low, high fluid temperature (increasing vapor pressure), excessive friction loss in suction piping, high elevation difference between cooling tower basin and pump suction. * Air Entrainment: Air leaking into suction piping.

Solutions: Increase static head on suction side, reduce friction loss in suction piping, lower fluid temperature (if possible), check for air leaks, ensure NPSHR < NPSHA [1].

9. Maintenance

Regular preventive maintenance is crucial for ensuring the long-term reliability, efficiency, and performance of condenser water systems.

9.1 Daily/Weekly Checks

  • Cooling Tower: Check water level, makeup water operation, fan operation, and general cleanliness. Monitor for unusual noises or vibrations.
  • Pumps: Check for leaks, unusual noises, or vibrations. Monitor discharge pressure and motor amperage.
  • Water Treatment: Verify chemical feed rates and blowdown operation. Check water quality parameters (pH, conductivity, inhibitor levels).

9.2 Monthly/Quarterly Tasks

  • Cooling Tower: Clean basin, inspect fill and drift eliminators, check spray nozzles, lubricate fan bearings (if applicable).
  • Pumps: Lubricate motor and pump bearings (if applicable), check coupling alignment, inspect mechanical seals for leaks.
  • Strainers: Clean condenser water strainers.
  • Valves: Exercise isolation valves to prevent seizing.

9.3 Annual/Bi-Annual Tasks

  • Cooling Tower: Thorough cleaning and descaling of fill and basin. Inspect structural components, fan blades, and motor. Perform eddy current testing on condenser tubes.
  • Chiller Condenser: Mechanically or chemically clean chiller condenser tubes to remove scale and fouling. This is critical for maintaining chiller efficiency.
  • Pumps: Overhaul pumps as needed, replace worn bearings, seals, and impellers. Perform vibration analysis.
  • Controls: Calibrate sensors and control devices. Review and optimize control sequences.

10. Standards and Codes

Several industry standards and codes govern the design, installation, and operation of condenser water systems, ensuring safety, efficiency, and performance.

  • ASHRAE (American Society of Heating, Refrigerating and Air-Conditioning Engineers): ASHRAE Handbooks (Fundamentals, HVAC Systems and Equipment, HVAC Applications) provide comprehensive guidelines for HVAC system design, including condenser water systems. Standards like ASHRAE 90.1 (Energy Standard for Buildings Except Low-Rise Residential Buildings) set minimum energy efficiency requirements, which often influence design choices for pumps, chillers, and cooling towers [8]. ASHRAE Guideline 14 provides guidance on measurement and verification of energy performance.
  • ASME (American Society of Mechanical Engineers): ASME codes, particularly those related to pressure piping (e.g., ASME B31.1 Power Piping, ASME B31.9 Building Services Piping), govern the design, materials, fabrication, installation, inspection, and testing of pressure piping systems, ensuring their structural integrity and safety.
  • ANSI (American National Standards Institute): ANSI approves standards developed by other organizations, including ASHRAE and ASME, making them national standards. For example, ANSI/ASHRAE standards are widely adopted.
  • AHRI (Air-Conditioning, Heating, and Refrigeration Institute): AHRI develops and publishes performance rating standards for HVACR equipment, including chillers (e.g., AHRI Standard 550/590 for Water-Chilling and Heat Pump Water-Heating Packages Using the Vapor Compression Cycle) and cooling towers (e.g., AHRI Standard 600 for Rating Commercial Comfort and Process Cooling Towers). Specifying AHRI-certified equipment ensures that performance data is accurate and verifiable.
  • Local Building Codes: Local and national building codes (e.g., International Mechanical Code, Uniform Mechanical Code) incorporate many of these industry standards and set legal requirements for HVAC system design and installation.

11. FAQ Section

Q1: What is the primary purpose of a condenser water system?

A1: The primary purpose of a condenser water system is to reject heat from a water-cooled chiller to the ambient environment, typically through a cooling tower. This process is essential for the chiller to efficiently cool water for air conditioning or process applications. The condenser water absorbs heat from the chiller's refrigerant and then transfers it to the atmosphere, allowing the refrigerant to condense and complete its cycle.

Q2: How does pipe sizing impact the efficiency of a condenser water system?

A2: Proper pipe sizing significantly impacts system efficiency. Undersized pipes lead to high fluid velocities, resulting in excessive friction loss, increased pressure drop, and higher pump energy consumption. This forces the pump to work harder, consuming more electricity. Conversely, overly large pipes increase initial installation costs and can lead to low fluid velocities, which may cause sedimentation of solids and air accumulation, potentially affecting system performance and water quality. Optimal pipe sizing balances initial cost with long-term operating efficiency by minimizing pressure drop while maintaining adequate flow velocities.

Q3: What is Net Positive Suction Head Available (NPSHA) and why is it important for condenser water pumps?

A3: Net Positive Suction Head Available (NPSHA) is the absolute pressure at the suction side of a pump, minus the vapor pressure of the liquid, converted to feet of liquid. It represents the pressure available to push water into the pump without it vaporizing (cavitating). NPSHA is crucial because if it falls below the Net Positive Suction Head Required (NPSHR) by the pump (a value provided by the manufacturer), cavitation will occur. Cavitation is the formation and collapse of vapor bubbles within the pump, causing noise, vibration, reduced performance, and severe damage to the pump impeller and casing. Ensuring NPSHA > NPSHR is critical for reliable pump operation and longevity.

Q4: What are the key control strategies for optimizing condenser water system energy consumption?

A4: Key control strategies focus on maintaining optimal condenser water temperatures for the chiller while minimizing pump and fan energy. This includes modulating cooling tower fan speed or cycling fans to maintain a desired condenser water supply temperature, often reset based on ambient wet-bulb temperature or chiller load. Variable frequency drives (VFDs) on condenser water pumps allow flow rates to be adjusted according to chiller load, significantly reducing pump energy at part-load. Advanced strategies involve chiller-tower optimization, where a building management system (BMS) continuously adjusts setpoints and fan/pump speeds to minimize the combined energy use of the entire plant.

Q5: Why is water treatment essential for open-circuit cooling towers?

A5: Water treatment is essential for open-circuit cooling towers because, as water evaporates to cool the system, dissolved solids concentrate in the remaining water. This concentration increases the risk of several problems: corrosion of metal components, scaling (mineral deposits) on heat exchange surfaces (like chiller condenser tubes), and biological growth (algae, bacteria, including Legionella). Without proper water treatment, these issues can lead to reduced heat transfer efficiency, increased energy consumption, equipment damage, higher maintenance costs, and potential health hazards. A comprehensive water treatment program, including chemical inhibitors, bleed-off, and filtration, mitigates these risks, extends equipment life, and maintains system performance.

12. Internal links

References

[1] EngProGuides. Condenser Water Pump Design Guide. Available at: https://www.engproguides.com/condenser-water-pump-design.html [2] Trane. Condenser Water System Savings: Optimizing flow rates. Available at: https://www.trane.com/content/dam/Trane/Commercial/global/products-systems/education-training/engineers-newsletters/waterside-design/adm-apn045-en_0912.pdf [3] CED Engineering. Module 10: HVAC Cooling Tower & Condensers. Available at: https://www.cedengineering.com/userfiles/M08-020%20-%20HVAC%20Hacks%20%E2%80%93%20Module%2010%20HVAC%20Cooling%20Tower%20&%20Condensers%20%E2%80%93%20Essential%20Tips%20&%20Thumb%20Rules%20-%20US.pdf [4] H2X Engineering. How To Size Water Pipes Correctly. Available at: https://www.h2xengineering.com/blogs/how-to-size-water-pipes/ [5] Johnson Controls. Condenser Water System (CPO) - Metasys. Available at: https://docs.johnsoncontrols.com/bas/r/Metasys/en-US/Controller-Tool-Help/16.0.1/Central-Cooling-with-Optimization-Applications/Central-Cooling-with-Optimization-Mechanical-System-Selection/Condenser-Water-System-CPO [6] ASHRAE Journal. Optimizing Design Control of Chilled Water Plants Part 2: Condenser Water Distribution System Design. Available at: https://www.scribd.com/document/377351596/ASHRAE-Journal-Optimizing-Design-Control-of-Chilled-Water-Plants-Part-2-Condenser-Water-Distribution-System-Design [7] Lando Chillers. Screw Chiller Commissioning, Startup and Shutdown Procedures. Available at: https://lando-chillers.com/screw-chiller-commissioning-startup-and-shutdown-procedures/ [8] ASHRAE. ASHRAE Design Guides. Available at: https://www.ashrae.org/technical-resources/bookstore/ashrae-design-guides